Distributed load conductor sizing calculator
Free distributed load conductor sizing calculator: get minimum area (drop only) from voltage, current and one-way cable length. With the formula shown.
Project inputs
Updates as inputs change. Unit changes preserve the same physical values.
Method & assumptions
Choose the next available size and separately check ampacity, fault withstand and terminals. 0.5 factor assumes a uniform distributed load; enter 1 for end load.
Results do not check every aspect of an electrical installation. The calculators follow US (NEC) practice only; a regional preset changes defaults such as voltage and units, and no result certifies NEC compliance.
Sources and validation →Worked example
Voltage: 120 V · Current: 20 A · One-way cable length: 100 ft · Resistivity at operating temperature: 12.9 Ω·cmil/ft · Allowed voltage drop: 3 % · Supply: Single phase · Effective length factor: 0.5
Minimum area (drop only): 7.167 kcmil
This example uses the stated inputs; results for the entered values appear above.Estimating and invoicing tool