Conduit fill calculator
Free conduit fill calculator: get fill and minimum internal diameter from conductor count, outside conductor diameter and internal conduit diameter.
Project inputs
Updates as inputs change. Unit changes preserve the same physical values.
Method & assumptions
Use outside insulated diameters. Verify jurisdictional limits; no automatic UK/Canadian application of NEC percentages.
Results do not check every aspect of an electrical installation. The calculators follow US (NEC) practice only; a regional preset changes defaults such as voltage and units, and no result certifies NEC compliance.
Sources and validation →Worked example
Conductor count: 4 · Outside conductor diameter: 0.212 in · Internal conduit diameter: 0.824 in · Verified fill limit: 40 %
Fill: 26.478 % · Minimum internal diameter: 0.67 in
This example uses the stated inputs; results for the entered values appear above.Estimating and invoicing tool