Maximum wire length (short-circuit)
Free maximum wire length (short-circuit): get maximum resistive loop length from voltage, required fault current for disconnection and external loop impedance.
Project inputs
Updates as inputs change. Unit changes preserve the same physical values.
Method & assumptions
Simplified equal line/return areas and resistive loop. Enter line-to-ground voltage. Excludes reactance and voltage correction.
Results do not check every aspect of an electrical installation. The calculators follow US (NEC) practice only; a regional preset changes defaults such as voltage and units, and no result certifies NEC compliance.
Sources and validation →Worked example
Voltage: 120 V · Required fault current for disconnection: 160 A · External loop impedance: 0.2 Ω · Conductor area: 6.53 kcmil · Resistivity at operating temperature: 12.9 Ω·cmil/ft
Maximum resistive loop length: 139.205 ft