CONDUCTORS · CALCULATOR
Power losses in cables
Free power losses in cables: get power loss from current, resistance per conductor and loaded conductors. The formula is shown; verify against the NEC.
US (NEC) only · NFPA 70 / NEC — locally adopted editionDefaults are US values. Verify the locally adopted NEC edition and project data.Official reference ↗
Project inputs
Measurements
Updates as inputs change. Unit changes preserve the same physical values.
Method & assumptions
Ploss = N × I² × R
Equal current and resistance per loaded conductor.
Results do not check every aspect of an electrical installation. The calculators follow US (NEC) practice only; a regional preset changes defaults such as voltage and units, and no result certifies NEC compliance.
Sources and validation →Worked example
Current: 20 A · Resistance per conductor: 0.2 Ω · Loaded conductors: 2
Power loss: 160 W