Cable protection from short-circuit
Free cable protection from short-circuit: get cable withstand from conductor area, verified material/insulation k factor, fault current and disconnection time.
Project inputs
Updates as inputs change. Unit changes preserve the same physical values.
Method & assumptions
Adiabatic approximation for short durations. Enter k from adopted code/material data; protective let-through energy may require manufacturer curves.
Results do not check every aspect of an electrical installation. The calculators follow US (NEC) practice only; a regional preset changes defaults such as voltage and units, and no result certifies NEC compliance.
Sources and validation →Worked example
Conductor area: 6.53 kcmil · Verified material/insulation k factor: 115 A√s/mm² · Fault current: 1,000 A · Disconnection time: 0.1 s
Cable withstand: 144,789.403 A²s · Fault energy: 100,000 A²s · Minimum adiabatic area: 5.427 kcmil