Maximum wire length (voltage drop)
Free maximum wire length (voltage drop): get maximum one-way length from voltage, current, conductor area, resistivity at operating temperature and drop limit.
Project inputs
Updates as inputs change. Unit changes preserve the same physical values.
Method & assumptions
Resistance-only, voltage-drop limit. Separately verify protection and ampacity.
Results do not check every aspect of an electrical installation. The calculators follow US (NEC) practice only; a regional preset changes defaults such as voltage and units, and no result certifies NEC compliance.
Sources and validation →Worked example
Voltage: 120 V · Current: 20 A · Conductor area: 6.53 kcmil · Resistivity at operating temperature: 12.9 Ω·cmil/ft · Drop limit: 3 % · Supply: Single phase
Maximum one-way length: 45.558 ft