Motor FLA calculator
Free motor FLA calculator: get estimated full-load current from output power, voltage and power factor. The formula is shown; verify against the NEC.
Project inputs
Updates as inputs change. Unit changes preserve the same physical values.
Method & assumptions
Use required adopted-code FLC tables for protection selection; engineering estimate only.
Results do not check every aspect of an electrical installation. The calculators follow US (NEC) practice only; a regional preset changes defaults such as voltage and units, and no result certifies NEC compliance.
Sources and validation →Worked example
Output power: 10 hp · Voltage: 230 V · Supply: Single phase · Power factor: 0.85 · Efficiency: 90 %
Estimated full-load current: 42.381 A
This example uses the stated inputs; results for the entered values appear above.Estimating and invoicing tool