Motor service factor calculator
Free motor service factor calculator: get service factor current from current, rated output, nameplate service factor and verified overload multiplier.
Project inputs
Updates as inputs change. Unit changes preserve the same physical values.
Method & assumptions
SF is a nameplate operating allowance, not a universal overload setting. Verify motor temperature rise, code and manufacturer.
Results do not check every aspect of an electrical installation. The calculators follow US (NEC) practice only; a regional preset changes defaults such as voltage and units, and no result certifies NEC compliance.
Sources and validation →Worked example
Current: 20 A · Rated output: 10 hp · Nameplate service factor: 1.15 · Verified overload multiplier: 1.25
Service factor current: 23 A · Service factor output: 11.5 hp · Overload arithmetic: 25 A