Power factor correction calculator
Free power factor correction calculator: get compensation required from active load, initial power factor and target power factor. With the formula shown.
Project inputs
Updates as inputs change. Unit changes preserve the same physical values.
Method & assumptions
Steady-state displacement correction. Target must exceed initial PF. Transformer no-load compensation requires manufacturer data; check resonance and harmonics.
Results do not check every aspect of an electrical installation. The calculators follow US (NEC) practice only; a regional preset changes defaults such as voltage and units, and no result certifies NEC compliance.
Sources and validation →Worked example
Active load: 30 kW · Initial power factor: 0.75 · Target power factor: 0.95
Compensation required: 16.597 kvar