Transformer power factor correction calculator
Free transformer power factor correction calculator: get compensation required from active load, initial power factor and target power factor.
Project inputs
Updates as inputs change. Unit changes preserve the same physical values.
Method & assumptions
Steady-state displacement correction. Target must exceed initial PF. Transformer no-load compensation requires manufacturer data; check resonance and harmonics.
Results do not check every aspect of an electrical installation. The calculators follow US (NEC) practice only; a regional preset changes defaults such as voltage and units, and no result certifies NEC compliance.
Sources and validation →Worked example
Active load: 30 kW · Initial power factor: 0.75 · Target power factor: 0.95
Compensation required: 16.597 kvar